Macromatic PLP Series - Phase Loss & Reversal Monitor Relays

Macromatic PLP Series - Phase Loss & Reversal Monitor Relays (Plug-In)
   
The PLP Series Phase Monitor Relays provide protection against phase loss & phase reversal in a compact plug-in design. The relay is energized and the LED on when all three phases are present and in the correct sequence. Any fault will instantaneously de-energize the relay and turn off the LED. Re-energization is automatic upon correction of the fault condition.

These devices are designed to be compatible with most Wye or Delta systems with no connection to Neutral required.
 
Features:
  • PLP Series protects against phase loss & phase reversal
  • LED indicates both normal and fault conditions
  • Compact plug-in case utilixing industry standard 8-pin octal socket
  • 10A SPDT output contacts
Macromatic PCP/PLP Representative Photo
Approvals Approvals
 
Click here for specifications and dimensions in .pdf formatPDF
Part Number Protects Against Nominal Voltage (50/60 Hz)
Phase to Phase (Line to Line)
Wiring Socket
Add part number PLP120 to your Quote. PLP120 Phase Reversal and Phase Loss 120V Diagram 23
Add part number PLP208 to your Quote. PLP208 Phase Reversal and Phase Loss 208V
Add part number PLP240 to your Quote. PLP240 Phase Reversal and Phase Loss 240V
Add part number PLP400 to your Quote. PLP400 Phase Reversal and Phase Loss 400V
Add part number PLP480 to your Quote. PLP480 Phase Reversal and Phase Loss 480V
*Requires a 600V-rated socket when used on system voltages above 300V.
 
Phase Loss: Unit trips on loss of any Phase A, B or C.
Phase Reversal: Unit trips if sequence of the three phases is anything other than A-B-C.
Output Contacts: 10A Resistive SPDT @ 240V AC, 1/3HP @ 120/240V AC (N.O.), 1/6HP @ 120/240V AC (N.C.)
Life: Full Load: 100,000 operations
Response Times: Operate: 50ms, Release: 50ms
Load (Burden): 3VA
Temperature: -28° to 65°C (-18° to 149°F)
Transient Protection: 10,000 volts for 20 microseconds
Mounting: Uses an 8 pin octal socket. Requires a 600V-rated socket when used on system voltages greater than 300V (Macromatic Product Number 70169-D
Indicator LED: Red LED on when all conditions are normal, and off when a fault condition has occurred.
Reset: Automatic upon correction of fault