Macromatic TR-6 Series Time Ranger™ Programmable Multi-Range Time Delay Relays

Macromatic TR-6 Series Time Ranger™ Programmable Multi-Range Time Delay Relays (Plug-In)
On Delay, Interval On, Flasher & True Off Delay Functions
   
Features:
  • Each unit has 16 timing ranges built-in (8 on True Off Delay)
  • Selecting a range is easy using a rotary switch (no math is required or DIP switches to set)
  • Timing ranges up to 2 hours (30 minutes on True Off Delay)
  • Uses industry-standard 8 pin octal sockets
  • 10A DPDT output contacts
Macromatic TR-6 Series  
All TR-6 Series
Approvals Approvals
All TR-6 Series Except TR-606
Approvals Approvals
TR-606 Only
Approvals
 
Click here for specifications and dimensions in .pdf format PDF
Part Number Function Input Voltage Wiring Socket
Add part number TR-60222 to your Quote. TR-60222 ON DELAY
(A)
120V AC/DC Diagram 1
Add part number TR-60226 to your Quote. TR-60226 12V AC/DC
Add part number TR-60228 to your Quote. TR-60228 24V AC/DC
Add part number TR-60221 to your Quote. TR-60221 240V AC
Add part number TR-60522 to your Quote. TR-60522 INTERVAL ON
(B)
120V AC/DC
Add part number TR-60526 to your Quote. TR-60526 12V AC/DC
Add part number TR-60528 to your Quote. TR-60528 24V AC/DC
Add part number TR-60521 to your Quote. TR-60521 240V AC
Add part number TR-60822 to your Quote. TR-60822 FLASHER (OFF 1st)
(E)
120V AC/DC
Add part number TR-60826 to your Quote. TR-60826 12V AC/DC
Add part number TR-60828 to your Quote. TR-60828 24V AC/DC
Add part number TR-60821 to your Quote. TR-60821 240V AC
Add part number TR-60922 to your Quote. TR-60922 FLASHER (ON 1st)
(F)
120V AC/DC
Add part number TR-60926 to your Quote. TR-60926 12V AC/DC
Add part number TR-60928 to your Quote. TR-60928 24V AC/DC
Add part number TR-60921 to your Quote. TR-60921 240V AC
Add part number TR-60622 to your Quote. TR-60622 TRUE OFF DELAY
(R)
120V AC/DC
Add part number TR-60626 to your Quote. TR-60626 12V AC/DC
Add part number TR-60628 to your Quote. TR-60628 24V AC/DC
Add part number TR-60621 to your Quote. TR-60621 240V AC
 
Timing Ranges
Select one of the 8 or 16 built-in time ranges by setting the rotary switch per a chart on the unit and adjust within that range using the knob on top:
 
TR-602, 605, 608 & 609 SERIES   TR-606 SERIES  
Dial Setting Timing Range
A 0.1-0.25 Sec
B 0.2-0.5 Sec
C 0.3-1 Sec
D 0.5-2 Sec
E 1-4 Sec
F 2-8 Sec
G 4-15 Sec
H 8-30 Sec
I 15-60 Sec
J 30-120 Sec
K 1-4 Min
L 2-8 Min
M 4-15 Min
N 8-30 Min
O 15-60 Min
P 30-120 Min
 
Dial Setting Timing range
A 0.05-5 Sec
B 0.1-10 Sec
C 0.3-30 Sec
D 0.6-60 Sec
E 1.8-180 Sec
F 3-300 Sec
G 0.1-10 Min
H 0.3-30 Min
 
 
Timing Functions
Code / Function Operation Timing Chart
(A) ON DELAY
Delay on Operate
Delay on Make
Upon application of input voltage, the time delay (t) begins. At the end of the time delay (t), the output is energized. Input voltage must be removed to reset the time delay relay & de-energize the output.. (A) ON DELAY
(B) INTERVAL ON
Interval
Upon application of input voltage, the output is energized and the time delay (t) begins. At the end of the time delay (t), the output is de-energized. Input voltage must be removed to reset the time delay relay. (B) INTERVAL ON
(E) FLASHER
(Off First)
Upon application of input voltage, the time delay (t) begins. At the end of the time delay (t), the output is energized and remains in that condition for the time delay (t). At the end of the time delay (t), the output is de-energized and the sequence repeats until input voltage is removed. (E) FLASHER - OFF 1ST
(F) FLASHER
(ON First)
Upon application of input voltage, the output is energized and the time delay (t) begins. At the end of the time delay (t), the output is de-energized and remains in that condition for the time delay (t). At the end of the time delay (t), the output is energized and the sequence repeats until input voltage is removed. (F) FLASHER - ON 1ST
(R) TRUE OFF DELAY Upon application of input voltage, the output is energized. When the input voltage is removed, the time delay (t) begins. At the end of the time delay (t), the output is deenergized. Input voltage must be applied for a minimum of 0.5 seconds to assure proper operation. Any application of the input voltage during the time delay (t) will reset the time delay. No external trigger is required. (R) TRUE OFF DELAY
 
Voltage Tolerance: AC Operation: +10/-15% of nominal at 50/60 Hz.
DC Operation: +10/-15% of nominal.
Load (Burden): 2 VA
Setting Accuracy: Maximum Setting (Adjustable): +5%, -0%
Minimum Setting (Adjustable): +0%, -50%
Repeat Accuracy: > 2 Seconds Delay ±0.1%
0.1 - 2 Seconds Delay ±2%
Reset Time: On Delay/Interval/Repeat Cycle/Delayed Interval: 0.1 Seconds
Off Delay/Single Shot/Watchdog/Triggered Delayed Interval: 0.04 Seconds
Start-up Time: (Time from when power is applied until unit is timing)
120 & 240V units 0.05 Seconds
12, 24 & 48V units 0.08 Seconds
Maintain Function Time: (Time unit continues to operate after power is removed) 0.01 Seconds for all units
Temperature: 12-120V Input Voltage: -28° to 65°C (-18° to 150°F)
240V Input Voltage: -28° to 50°C (-18° to 122°F)
Triggering Off Delay, Single Shot or Watchdog Units: Timing sequence must be initiated only after input voltage is applied to unit. Minimum required trigger switch closure time is 0.1 seconds.
Compatibility: Using a solid state switch to initiate the time sequence is acceptable. See www.macromatic.com/leakage for information regarding leakage current limits and other solid state design considerations.
Output Contacts (All TR-6 Series Products except TR-606 True Off Delay): DPDT 10A @ 240V AC/30V DC, 1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240V AC (N.C.) B300 & R300; AC15 & DC13
Output Contacts (TR-606 True Off Delay): DPDT 10A @ 240V AC; 8A @ 28V DC, 1/2 HP @ 240V AC, 1/4HP @ 120V AC B300 & R300
Life: Mechanical: 10,000,000 operations (2,000,000 operations on TR-606 Series only)
Full Load: 100,000 operations
IMPORTANT FOR TR-606 SERIES ONLY: These relays are shipped from the factory in the OFF state. A shock to the relay during shipping or installation may cause it to change to the ON state. It is recommended that input voltage be applied to the product for at least 0.1 second and removed to cycle the unit to the OFF state prior to use in the application. Please note that it will take as long as the OFF Delay setting to reset the unit once input voltage has been removed.