Macromatic TR-6 Series Time Ranger™ Programmable Multi-Range Time Delay Relays

Macromatic TR-6 Series Time Ranger™ Programmable Multi-Range Time Delay Relays (Plug-In)
Repeat Cycle & Delayed Interval Functions
   
Features:
  • Each unit has 16 timing ranges built-in
  • Selecting a range is easy using a rotary switch (no math is required or DIP switches to set)
  • Timing ranges up to 24 hours
  • Independently selectable & adjustable ON & OFF times
  • Uses industry-standard 8 or 11 pin octal sockets
  • 10A DPDT output contacts
Macromatic TR-6 Series
Approvals Approvals Approvals Approvals
 
Click here for specifications and dimensions in .pdf format PDF
Part Number Function Input Voltage Wiring Socket
Add part number TR-63122 to your Quote. TR-63122 REPEAT CYCLE
(OFF Time First Followed by ON Time and Repeating)
(L)
120V AC/DC Diagram 1
Add part number TR-63126 to your Quote. TR-63126 12V AC/DC
Add part number TR-63128 to your Quote. TR-63128 24V AC/DC
Add part number TR-63121 to your Quote. TR-63121 240V AC
Add part number TR-65122 to your Quote. TR-65122 REPEAT CYCLE
(ON Time First Followed by OFF Time and Repeating)
(M)
120V AC/DC
Add part number TR-65126 to your Quote. TR-65126 12V AC/DC
Add part number TR-65128 to your Quote. TR-65128 24V AC/DC
Add part number TR-65121 to your Quote. TR-65121 240V AC
Add part number TR-66122 to your Quote. TR-66122 DELAYED INTERVAL
(OFF Time First Followed by ON Time Follwed by OFF State Until Reset)
(N)
120V AC/DC
Add part number TR-66126 to your Quote. TR-66126 12V AC/DC
Add part number TR-66128 to your Quote. TR-66128 24V AC/DC
Add part number TR-66121 to your Quote. TR-66121 240V AC
Add part number TR-66522 to your Quote. TR-66522 DELAYED INTERVAL
Control Switch Trigger
(OFF Time First Followed by ON Time Follwed by OFF State Until Reset)
(P)
120V AC/DC Diagram 2
Add part number TR-66526 to your Quote. TR-66526 12V AC/DC
Add part number TR-66528 to your Quote. TR-66528 24V AC/DC
Add part number TR-66521 to your Quote. TR-66521 240V AC
These units have independently selectable & adjustable ON & OFF times.
 
Timing Ranges
Select one of the 16 built-in time ranges by setting the rotary switch per a chart on the unit and adjust within that range using the knob on top:
 
TR-631, 651, 661 & 665 SERIES      
Dial Setting Timing Range
A 0.6-2.5 Sec
B 1.5-5 Sec
C 2.5-10 Sec
D 5-21 Sec
E 10-42 Sec
F 0.4-1.4 Min
G 0.7-2.8 Min
H 1.5-5.5 Min
I 3-11 Min
J 5.5-22.5 Min
K 11-45 Min
L 0.4-1.5 Hr
M 0.8-3 Hr
N 1.5-6 Hr
O 3-12 Hr
P 6-24 Hr
     
 
Timing Functions
Code / Function Operation Timing Chart
(L) REPEAT CYCLE
(OFF 1st)
Upon application of input voltage, the time delay (t1) begins. At the end of the time delay (t1), the output is energized and remains in that condition for the time delay (t2). At the end of this time delay, the output is de-energized and the sequence repeats until input voltage is removed. (L) REPEAT CYCLE - OFF 1ST
(M) REPEAT CYCLE
(ON 1st)
Upon application of input voltage, the output is energized and the time delay (t1) begins. At the end of the time delay (t1), the output is de-energized and remains in that condition for the time delay (t2). At the end of this time delay, the output is energized and the sequence repeats until input voltage is removed. (M) REPEAT CYCLE - ON 1ST
(N) DELAYED INTERVAL
Single Cycle
Upon application of input voltage, the time delay (t1) begins. At the end of the time delay (t1), the output is energized and remains in that condition for the time delay (t2). At the end of this time delay (t2), the output is de-energized. Input voltage must be removed to reset the time delay relay. (N) DELAYED INTERVAL
(P) TRIGGERED DELAYED INTERVAL Upon application of input voltage, the time delay relay is ready to accept a trigger. When the trigger is applied, the time delay (t1) begins. At the end of the time delay (t1), the output is energized and remains in that condition for the time delay (t2). At the end of the time delay (t2), the output is de-energized & the relay is ready to accept another trigger. During both time delay (t1) & time delay (t2), the trigger is ignored. (P) DELAYED INTERVAL - CONTROL SWITCH TRIGGERED
 
Voltage Tolerance: AC Operation: +10/-15% of nominal at 50/60 Hz.
DC Operation: +10/-15% of nominal.
Load (Burden): 2 VA
Setting Accuracy: Maximum Setting (Adjustable): +5%, -0%
Minimum Setting (Adjustable): +0%, -50%
Repeat Accuracy: > 2 Seconds Delay ±0.1%
0.1 - 2 Seconds Delay ±2%
Reset Time: On Delay/Interval/Repeat Cycle/Delayed Interval: 0.1 Seconds
Off Delay/Single Shot/Watchdog/Triggered Delayed Interval: 0.04 Seconds
Start-up Time: (Time from when power is applied until unit is timing)
120 & 240V units 0.05 Seconds
12, 24 & 48V units 0.08 Seconds
Maintain Function Time: (Time unit continues to operate after power is removed) 0.01 Seconds for all units
Temperature: 12-120V Input Voltage: -28° to 65°C (-18° to 150°F)
240V Input Voltage: -28° to 50°C (-18° to 122°F)
Triggering Off Delay, Single Shot or Watchdog Units: Timing sequence must be initiated only after input voltage is applied to unit. Minimum required trigger switch closure time is 0.1 seconds.
Compatibility: Using a solid state switch to initiate the time sequence is acceptable. See www.macromatic.com/leakage for information regarding leakage current limits and other solid state design considerations.
Output Contacts (All TR-6 Series Products except TR-606 True Off Delay): DPDT 10A @ 240V AC/30V DC, 1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240V AC (N.C.) B300 & R300; AC15 & DC13
Output Contacts (TR-606 True Off Delay): DPDT 10A @ 240V AC; 8A @ 28V DC, 1/2 HP @ 240V AC, 1/4HP @ 120V AC B300 & R300
Life: Mechanical: 10,000,000 operations (2,000,000 operations on TR-606 Series only)
Full Load: 100,000 operations
IMPORTANT FOR TR-606 SERIES ONLY: These relays are shipped from the factory in the OFF state. A shock to the relay during shipping or installation may cause it to change to the ON state. It is recommended that input voltage be applied to the product for at least 0.1 second and removed to cycle the unit to the OFF state prior to use in the application. Please note that it will take as long as the OFF Delay setting to reset the unit once input voltage has been removed.