Connex-Electronics.com
Macromatic
Macromatic TR-6 Series Time Ranger™ Programmable Multi-Range Time Delay Relays

Macromatic TR-6 Series Time Ranger™ Programmable Multi-Range Time Delay Relays (Plug-In)
OFF Delay, Single Shot & Watchdog Functions
   
Features:
  • Each unit has 16 timing ranges built-in
  • Selecting a range is easy using a rotary switch (no math is required or DIP switches to set)
  • Timing ranges up to 2 hours
  • Uses industry-standard 11 pin octal sockets
  • 10A DPDT output contacts
Macromatic TR-6 Series
Approvals Approvals Approvals Approvals
 
Click here for specifications and dimensions in .pdf format PDF
Part Number Function Input Voltage Wiring Socket
Add part number TR-61622 to your Quote. TR-61622 OFF DELAY
Control Switch Trigger
(C)
120V AC/DC Diagram 2
Add part number TR-61626 to your Quote. TR-61626 12V AC/DC
Add part number TR-61628 to your Quote. TR-61628 24V AC/DC
Add part number TR-61621 to your Quote. TR-61621 240V AC
Add part number TR-61522 to your Quote. TR-61522 SINGLE SHOT
Control Switch Trigger
(D)
120V AC/DC
Add part number TR-61526 to your Quote. TR-61526 12V AC/DC
Add part number TR-61528 to your Quote. TR-61528 24V AC/DC
Add part number TR-61521 to your Quote. TR-61521 240V AC
Add part number TR-61322 to your Quote. TR-61322 WATCHDOG
Control Switch Trigger (Retriggerable Single Shot)
(J)
120V AC/DC
Add part number TR-61326 to your Quote. TR-61326 12V AC/DC
Add part number TR-61328 to your Quote. TR-61328 24V AC/DC
Add part number TR-61321 to your Quote. TR-61321 240V AC
Add part number TR-61922 to your Quote. TR-61922 OFF DELAY
Power Trigger
(C)
120V AC/DC Diagram 4
Add part number TR-61926 to your Quote. TR-61926 12V AC/DC
Add part number TR-61928 to your Quote. TR-61928 24V AC/DC
Add part number TR-61921 to your Quote. TR-61921 240V AC
Add part number TR-61722 to your Quote. TR-61722 SINGLE SHOT
Power Trigger
(D)
120V AC/DC
Add part number TR-61726 to your Quote. TR-61726 12V AC/DC
Add part number TR-61728 to your Quote. TR-61728 24V AC/DC
Add part number TR-61722 to your Quote. TR-61722 240V AC
Add part number TR-61822 to your Quote. TR-61822 WATCHDOG
Power Trigger (Retriggerable Single Shot)
(J)
120V AC/DC
Add part number TR-61826 to your Quote. TR-61826 12V AC/DC
Add part number TR-61828 to your Quote. TR-61828 24V AC/DC
Add part number TR-61821 to your Quote. TR-61821 240V AC
 
Timing Ranges
Select one of the 16 built-in time ranges by setting the rotary switch per a chart on the unit and adjust within that range using the knob on top:
 
TR-613, 615, 616, 617, 618 & 619 SERIES      
Dial Setting Timing Range
A 0.1-0.25 Sec
B 0.2-0.5 Sec
C 0.3-1 Sec
D 0.5-2 Sec
E 1-4 Sec
F 2-8 Sec
G 4-15 Sec
H 8-30 Sec
I 15-60 Sec
J 30-120 Sec
K 1-4 Min
L 2-8 Min
M 4-15 Min
N 8-30 Min
O 15-60 Min
P 30-120 Min
     
 
Timing Functions
Code / Function Operation Timing Chart
(C) OFF DELAY
Delay on Release
Delay on Break
Delay on De- Energization
Upon application of input voltage, the time delay relay is ready to accept a trigger. When the trigger is applied, the output is energized. Upon removal of the trigger, the time delay (t) begins. At the end of the time delay (t), the output is de-energized. Any application of the trigger during the time delay will reset the time delay (t) and the output remains energized. (C) OFF DELAY
(D) SINGLE SHOT
One Shot
Momentary Interval
Upon application of input voltage, the time delay relay is ready to accept a trigger. When the trigger is applied, the output is energized and the time delay (t) begins. During the time delay (t), the trigger is ignored. At the end of the time delay (t), the output is de-energized and the time delay relay is ready to accept another trigger. (D) SINGLE SHOT
(J) WATCHDOG
Retriggerable Single Shot
Upon application of input voltage, the time delay relay is ready to accept a trigger. When the trigger is applied, the output is energized and the time delay (t) begins. At the end of the time delay (t), the output is de-energized unless the trigger is removed and re-applied prior to time out (before time delay (t) elapses). Continuous cycling of the trigger at a rate faster than the time delay (t) will cause the output to remain energized indefinitely. (J) WATCHDOG
 
Voltage Tolerance: AC Operation: +10/-15% of nominal at 50/60 Hz.
DC Operation: +10/-15% of nominal.
Load (Burden): 2 VA
Setting Accuracy: Maximum Setting (Adjustable): +5%, -0%
Minimum Setting (Adjustable): +0%, -50%
Repeat Accuracy: > 2 Seconds Delay ±0.1%
0.1 - 2 Seconds Delay ±2%
Reset Time: On Delay/Interval/Repeat Cycle/Delayed Interval: 0.1 Seconds
Off Delay/Single Shot/Watchdog/Triggered Delayed Interval: 0.04 Seconds
Start-up Time: (Time from when power is applied until unit is timing)
120 & 240V units 0.05 Seconds
12, 24 & 48V units 0.08 Seconds
Maintain Function Time: (Time unit continues to operate after power is removed) 0.01 Seconds for all units
Temperature: 12-120V Input Voltage: -28° to 65°C (-18° to 150°F)
240V Input Voltage: -28° to 50°C (-18° to 122°F)
Triggering Off Delay, Single Shot or Watchdog Units: Timing sequence must be initiated only after input voltage is applied to unit. Minimum required trigger switch closure time is 0.1 seconds.
Compatibility: Using a solid state switch to initiate the time sequence is acceptable. See www.macromatic.com/leakage for information regarding leakage current limits and other solid state design considerations.
Output Contacts (All TR-6 Series Products except TR-606 True Off Delay): DPDT 10A @ 240V AC/30V DC, 1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240V AC (N.C.) B300 & R300; AC15 & DC13
Output Contacts (TR-606 True Off Delay): DPDT 10A @ 240V AC; 8A @ 28V DC, 1/2 HP @ 240V AC, 1/4HP @ 120V AC B300 & R300
Life: Mechanical: 10,000,000 operations (2,000,000 operations on TR-606 Series only)
Full Load: 100,000 operations
IMPORTANT FOR TR-606 SERIES ONLY: These relays are shipped from the factory in the OFF state. A shock to the relay during shipping or installation may cause it to change to the ON state. It is recommended that input voltage be applied to the product for at least 0.1 second and removed to cycle the unit to the OFF state prior to use in the application. Please note that it will take as long as the OFF Delay setting to reset the unit once input voltage has been removed.