| Wago Fieldbus Coupler - ETHERNET TCP/IP 10 Mbits/s |
 |
| Part Number |
Conformity Marking |
Approvals |
750-342 |
 |
cULus, ABS*, BV*, DNV*, GL*, LR*, RINA*, cULus-EX, KEMA |
750-626 filter module is absolutely necessary |
| ETHERNET TCP/IP FIELDBUS COUPLER 10 MBit/s CARRIER RAIL DIN 35 CAGE CLAMP CONNECTION |
The ETHERNET TCP/IP fieldbus coupler supports a number of network protocols to send process data via ETHERNET TCP/IP. By observing the relevant IT standards, connection to existing local or global networks (LAN, Internet) is possible without any problem.
Using ETHERNET as a fieldbus makes universal data transmission between the factory and the office possible. Morover, the ETHERNET TCP/IP fieldbus coupler offers remote maintenance, i.e. processes can be contolled regardless of the location.
Process data exchange is done using the MODBUS/TCP protocol. The buscoupler supports all I/O modules and automatically configures, creating a local process image.
The HTML pages that are stored in the fieldbus coupler allow access to information on configuration, status, or I/O data of the ETHERNET TCP/IP fieldbus coupler. Only a standard WEB browser is required. Through the dynamic configuration of the IP addresses via BootP server designing the network becomes very easy and flexible. |
|
| Technical Information |
| Characteristic |
Value |
| Max. no. of nodes |
limited by ETHERNET- Specification |
| Transmission medium |
Twisted Pair S-UTP 100 Ohm Cat 5 |
| Buscoupler connection |
RJ45 |
| Max. length of fieldbus segment |
100 m between hub and
750-342 max. length of network limited by Ethernet specification |
| Baud rate |
10 Mbits/s |
| Protocols |
MODBUS/TCP, HTTP, BootP, MODBUS/UDP |
| UL 508 |
E175199, UL 508 |
| Conformity marking |
CE |
| Max. no. of I/O modules |
64 |
| Max. fieldbus input image (Byte) |
512 Byte |
| Max. fieldbus output image (Byte) |
512 Byte |
| Max. number of socket connections |
1 HTTP3 MODBUS / TCP |
| Voltage supply |
DC 24 V (-25% / + 30%) |
| Input current (max) |
500 mA |
| Efficiency of the power supply |
87% |
| Internal current consumption |
200 mA |
| Total current for the I/O modules |
1800 mA |
| Isolation |
500 V system / supply |
| Voltage via power jumper contacts (max) |
DC 24 V (-25% / + 30%) |
| Current via power jumper contacts (max) |
DC 10 A |
|
| Characteristic |
Value |
| Operating temperature |
0 °C ... + 55 °C |
| Storage temperature |
-25 °C ... +85 °C |
| Relative air humidity |
95% |
| Vibration resistance |
acc. IEC 60068-2-6 |
| Shock resistance |
acc. IEC 60068-2-27 |
| Degree of protection |
IP 20 |
| EMC immunity to interference |
acc. EN 50082-2 (96) |
| EMC emission of interference |
per EN 50081-1 (93) |
| EMC marine applications - noise proof |
gem. Germanischer Lloyd (1997) |
| EMC marine applications - noise transmission |
gem. Germanischer Lloyd (1997) |
| Cross section from [mm²] |
0.08 mm² |
| Cross section to [mm²] |
2.5 mm² |
| Cross section from [AWG] |
28 AWG |
| Cross section to [AWG] |
14 AWG |
| Weight |
197 g |
| Color |
light gray |
| Height |
65 mm |
| Height |
2.56 in |
| Width |
51 mm |
| Width |
2.008 in |
| Depth |
100 mm |
| Depth |
3.937 in |
| Strip length from |
8 mm |
| Strip length to |
9 mm |
| Strip length |
0.33 in |
|
|