| Wago Main Page |
| I/O Products |
|
| Fieldbus Coupler |
| Programmable Feildbus Controller |
| Digital Input Modules |
 |
| 1 Channel |
| NAMUR,
EEx i |
| 2 Channel |
| 24V DC, 3.0 ms |
| 24V DC, 0.2 ms |
| 24V DC, 3.0 ms, proximity
switch |
| 24V DC, 0.2 ms, proximity
switch |
| 24V DC, 3.0 ms, diagnostics,
acknowledgment |
| 24V DC, 3.0 ms, diagnostics |
| 24V DC, intruder detection |
| 48V DC, 3.0 ms |
| 110V DC, high-side/low-side
switching |
| 120V DC |
| 230V DC |
| NAMUR |
| 4 Channel |
| 5V DC, 0.2 ms |
| 24V DC, 3.0 ms |
| 24V DC, 0.2 ms |
| 24V DC, 3.0 ms, 2-conductor |
| 24V DC, 0.2 ms, 2-conductor |
| 24V DC, pulse extension |
| 24V DC, 3.0 ms, low-side switching |
| 24V DC, 0.2 ms, low-side switching |
| 24V AC/DC, 20 ms |
| 24V AC/DC, pow. contacts 50 ms |
| 42V AC/DC |
| 8 Channel |
| 24V DC, 3.0 ms |
| 24V DC, 0.2 ms |
|
|
| Digital Output Modules |
| Analog Input Modules |
| Analog Output Modules |
| Specialty Modules |
| System Modules |
| Approvals |
|
| Wago Digital Input Modules |
 |
| Part Number |
Conformity Marking |
Approvals |
750-435 |
 |
TÜV (EEx i) |
Only use this modue lin connection with the 24V DC EEx i supply module (
750-625 ) |
| 1-CHANNEL DIGITAL INPUT MODULE NAMUR |
The digital input module receives the binary signals from sensors operating in hazardous environments of Zones 0 and 1. Namur sensors, optocouplers, mechanical contacts or other actuating elements can be connected by means of approved intrinsically safe devices. The WAGO-I/O-SYSTEM 750 has to be installed in Zone 2 or in non-hazardous environments. Each sensor is supplied with a short-circuit-protected 8.2 V supply. Indicators: Green LED (signal on /off) Red LED(short circuit, wire breakage) An optocoupler is used for electrical isolation between the bus and the field side. Note: Only use the digital input module in connection with the 24 V DC EEx i supply module
750-625 . |
|
| Power Supply Instructions |
When operating the intrinsically safe EEx i modules in connection with sensors/ actuators operating in hazardous environments of Zones 0 and 1, the supply module 24V DCEEx i (
750-625 ) must be used to supply the I/O modules.
Note: If further 24V DC EEx i supply modules are required, four separation modules (
750-616 ) must be placed between the intrinsically safe sections. |
|
| Technical Information |
| Characteristic |
Value |
| No. of inputs |
1 |
| Intrinsically safe per |
Eex ia/ib |
| CURRENT CONSUMPTION (INTERNAL) mA |
2.5 mA |
| Voltage via power jumper contacts (max) |
SUPPLY VIA DC 24.7 V EEX I SUPPLY MODULE
750-625 |
| Sensor supply Uv1,2 |
DC 8.2 V |
| Signal current (0) (<) |
1.2 mA |
| Signal current (1) (>) |
2.1 mA |
| Input filter (ms) |
3 ms |
| SWITCHING HYSTERESIS (mA) |
0.2 mA |
| Open-circuit voltage |
DC 8,2 V |
| Input resistance |
1kOhm |
| Length of input pulse |
>= 5 ms |
| Input pulse interval |
>= 3 ms |
| Short-circuit current |
< 8.2 mA |
| Short circuit monitoring |
> 6,4 mA |
| Wire break monitoring |
< 0,2 mA |
| Frequency (Hz) |
100 Hz |
| Power consumption P max. (W) |
0.5 W |
| Input current typ. (field side) |
13 mA + load |
| Heat dissipation |
0.5 W |
| Isolation |
375 V System / Supply |
| Internal data width |
2 BITS; -1 BIT INPUT; -1 BIT ERROR (SHORT CIRCUIT/OPEN CIRCUIT) |
| Operating temperature |
0 °C ... + 55 °C |
| Storage temperature |
-25 °C ... +85 °C |
| Relative air humidity |
95% |
| Vibration resistance |
acc. IEC 60068-2-6 |
| Shock resistance |
acc. IEC 60068-2-27 |
| Degree of protection |
IP 20 |
|
| Characteristic |
Value |
| EMC immunity to interference |
gem. EN 61000-6-2 (1999) |
| EMC emission of interference |
gem. EN 61000-6-4 (2002) |
| Conformity marking |
CE |
| EC EMC standards |
89 / 336 / EWG |
| EC low voltage standards |
73 / 23 / EWG |
| Ex guideline |
94 / 9 / EG; EN 50014, EN 50020, EN 50021 |
| Marking |
Ex II 3 (1) GD EEx nA [ia] IIC / IIB T4 |
| Electrical circuit, relevant safety data |
U0 = 12 V; I0 = 16 mA; P0 = 48 mW; CHARACTERISTIC: LINEAR |
| Intrinsically safe / EEx ib IIB / EEx ib IIC |
L0 / 560 mH / 180 mH |
| Intrinsically safe / EEx ib IIB / EEx ib IIC |
C0 / 9 ?F / 1,4 ?F |
| Cross section from [mm²] |
0.08 mm² |
| Cross section to [mm²] |
2.5 mm² |
| Cross section from [AWG] |
28 AWG |
| Cross section to [AWG] |
14 AWG |
| Weight |
48.5 g |
| Color |
blue |
| Height |
64 mm |
| Height |
2.52 in |
| Width |
12 mm |
| Width |
0.472 in |
| Depth |
100 mm |
| Depth |
3.937 in |
| Strip length from |
8 mm |
| Strip length to |
9 mm |
| Strip length |
0.33 in |
|
|
|