						  The voltage ratings of terminal blocks are based upon
							 the minimum spacing between electrically conductive parts line to line through
							 air and over surface and line to ground through air and over surface.
							 
								- Class A: Service,
								  including deadfront switchboards, panel boards, service equipment and the
								  like.
 
								- Class B: Commercial
								  appliances including business equipment, electronic data processing equipment
								  and the like.
 
								- Class C: Industrial,
								  general
 
							   | 
						
						
						  Spacing Requirements (in
							 inches):
							 
								
								  
									 |   | 
									 Voltage  | 
									 Thru Air  | 
									 Over Surface  | 
								   
								  
									 | Class A  | 
									 51-150 151-300 301-600  | 
									 0.500 0.750 1.000  | 
									 0.750 1.250 2.000  | 
								   
								  
									 | Class B  | 
									 51-150 151-300 301-600 | 
									 0.063 0.094 0.375  | 
									 0.063 0.094 0.500  | 
								   
								  
									 | Class C  | 
									 51-150 151-300 301-600  | 
									 0.125 0.250 0.375  | 
									 0.250 0.375 0.500  | 
								   
								
							   |