| Wago Analog Input Modules |
 |
| Part Number |
Conformity Marking |
Approvals |
750-474 |
 |
cULus, ABS, BV, DNV, GL, LR, RINA, cULus-EX, KEMA |
| Data format for S5 control with FB 250: |
750-474/000-200 |
| 16 bit single-ended 60 Hz : |
750-474/005-000 |
|
| 2-CHANNEL ANALOG INPUT MOUDLE 4-20 mA CARRIER RAIL DIN 35 CAGE CLAMP CONNECTION |
| The analog input module is able to provide power to the field device, receive the transmitted analog signals, and with electrical isolation, transmit them to the fieldbus. The 24 V supply is derived from the power jumper con-tacts. The shield (screen) is directly connected to the DIN rail. At approx. 25 mA the overload protection switches the measurement input to a high resistance state. Under normal operating conditions it is automatically switched back. This input module can supply the voltage for 2-conductor transducers. |
|
| Technical Information |
| Characteristic |
Value |
| No. of inputs |
2 |
| Voltage supply |
via system voltage DC / DC |
| CURRENT CONSUMPTION (INTERNAL) mA |
75 mA |
| Input voltage |
non-linear, overload-protected; U = 1.2V + 160 Ohm x I mess |
| Signal current |
4 - 20 mA |
| Input voltage max. (V) |
24 V |
| Input resistance |
< 220 Ohm/ 20 mA |
| Overvoltage protection |
30 V polarity reversal protection |
| Resolution (Bit) |
15 Bit |
| Conversion time (typ) |
80 ms |
| Measuring error (25°) |
< +/- 0.1 % of the full scale value |
| Temperature coefficient |
< +/- 0.01 % / K of the full scale value |
| Isolation |
500 V system / supply |
| Data size |
2 x 16 Bit Data2 x 8 Bit control / status (optional) |
| Input filter (Hz) |
50 Hz |
| Noise rejection at sampling frequency |
< -100 dB |
| Noise rejection above sampling frequency |
< -40 dB |
| Operating temperature |
0 °C ... + 55 °C |
| Storage temperature |
-25 °C ... +85 °C |
| Relative air humidity |
95% |
| Vibration resistance |
acc. IEC 60068-2-6 |
| Shock resistance |
acc. IEC 60068-2-27 |
|
| Characteristic |
Value |
| Degree of protection |
IP 20 |
| EMC immunity to interference |
acc. EN 50082-2 (96) |
| EMC emission of interference |
per EN 50081-1 (93) |
| UL 508 |
E175199, UL 508 |
| EMC marine applications - noise proof |
gem. Germanischer Lloyd (1997) |
| Conformity marking |
CE |
| EMC marine applications - noise transmission |
gem. Germanischer Lloyd (1997) |
| Cross section from [mm²] |
0.08 mm² |
| Cross section to [mm²] |
2.5 mm² |
| Cross section from [AWG] |
28 AWG |
| Cross section to [AWG] |
14 AWG |
| Voltage CSA |
24 V |
| Weight |
55.5 g |
| Color |
light gray |
| Height |
64 mm |
| Height |
2.52 in |
| Width |
12 mm |
| Width |
0.472 in |
| Depth |
100 mm |
| Depth |
3.937 in |
| Strip length from |
8 mm |
| Strip length to |
9 mm |
| Strip length |
0.33 in |
|
|