| Wago Analog Input Modules |
 |
| Part Number |
Conformity Marking |
Approvals |
750-460 |
 |
cULus |
| 4-CHANNEL ANALOG INPUT MOUDLE PT 100 / RTD CARRIER RAIL DIN 35 CAGE CLAMP CONNECTION |
| The RTD (resistive temperature device) input module allows the direct connection of Pt or Ni resistance sensors. Only 2-conductor sensors can be connected. The module linearizes the entire temperature range automatically. A sensor error is indicated by a red LED. |
|
| Technical Information |
| Characteristic |
Value |
| Temperature range |
-200 °C ... + 850 °C (Pt) -60 °C ... +250 °C (Ni) |
| No. of inputs |
4 |
| Current consumption (mA) |
65 mA |
| Sensor types |
PT 100 (FACTORY PRESET), PT 200, PT 500, PT 1000, NI 100, RESISTANCE MEASURING |
| Measuring current typ. |
0.5 mA |
| Sensor connection |
2-conductor |
| Resolution (over the complete area) |
0,1 °C |
| Measuring error (25°) |
< +/- 0,1 °C |
| Conversion time |
on request |
| UL 508 |
E175199, UL 508 |
| Conformity marking |
CE |
| Voltage supply |
via system voltage DC / DC |
| Isolation |
400 V system / supply |
| Data size |
4 x 16 Bit data ;4 x 8 Bit controller / status (optional) |
| Operating temperature |
0 °C ... + 55 °C |
| Storage temperature |
-25 °C ... +85 °C |
| Relative air humidity |
95% |
|
| Characteristic |
Value |
| Vibration resistance |
acc. IEC 60068-2-6 |
| Shock resistance |
acc. IEC 60068-2-27 |
| Degree of protection |
IP 20 |
| EMC immunity to interference |
acc. EN 50082-2 (96) |
| EMC emission of interference |
per EN 50081-1 (93) |
| Cross section from [mm²] |
0.08 mm² |
| Cross section to [mm²] |
2.5 mm² |
| Cross section from [AWG] |
28 AWG |
| Cross section to [AWG] |
14 AWG |
| Weight |
55 g |
| Color |
light gray |
| Height |
64 mm |
| Height |
2.52 in |
| Width |
12 mm |
| Width |
0.472 in |
| Depth |
100 mm |
| Depth |
3.937 in |
| Strip length from |
8 mm |
| Strip length to |
9 mm |
| Strip length |
0.33 in |
|
|