| Technical Data |
| Input Specifications |
| Rated input voltage |
3 x 400...3 x 500 V AC (wide-range input) |
| AC input voltage range |
3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC |
| AC frequency range |
47...63 Hz |
| DC input voltage range |
450...800 V DC (max. 500 V DC acc. to UL508) |
| AC current consumption |
0.5 A @ 3 x 500 V AC / 0.6 A @ 3 x 400 V AC |
| DC current consumption |
0.4 A @ 800 V DC / 0.7 A @ 450 V DC |
| Input fuse (internal)/Inrush current |
no |
| Circuit Protection |
2 A / DI, safety fuse 2...3 A, Char. C, Circuit breaker |
| Output Specifications |
| Rated output voltage |
24 V DC ± 1 % |
| Output voltage |
22.5
29.5 V DC (adjustable via potentiometer on front) |
| Residual ripple, switching peaks |
100 mV ss @ 24 V DC, IN |
| Rated output current @ V rated |
10 A @ 60 °C |
| Continuous output current @ 24 V DC |
12 A @ 45 °C 11 A @ 55 °C 7.5 A @ 70 °C |
| Power boost @ 24 V DC, 60 °C |
6 A for 1 min, ED=5 %12 A for 1 min, ED=5 % |
| General Specifications |
| Efficiency |
> 90 % @ 3 x 500 V AC / > 90 % @ 3 x 400 V AC |
| Power factor (approx.) |
> 0.75 @ 3 x 500 V AC / > 0.78 @ 3 x 400 V AC |
| Mains buffering @ I rated |
> 25 ms @ 3 x 500 V AC / > 20 ms @ 3 x 400 V AC |
| Parallel connection option |
yes |
| Length x Width x Height mm |
125 x 60 x 130 |
| Weight |
0.9 kg |
| Approvals/Certifications |
| |
CE, cURus, UL508, CSA22.2 no.107 |
| Connection Data |
Input |
Output |
| Type of connection |
Screw connection |
Screw connection |
| Number of terminals |
4 for L1/L2/L3/PE |
5 (++/--) |
| Conductor cross-section, rigid min/max mm² |
0.5 / 6 |
0.5 / 6 |
| Conductor cross-section, flexible min/max mm² |
0.5 / 2.5 |
0.5 / 2.5 |
| Conductor cross-section, AWG/kcmil min/max |
26 / 12 |
26 / 12 |
| |
| Recommendation applies only for AC operation; the max. permissible operating voltage is to be observed in all cases! |