DK6 / I-I, Combi-foot, TS 35/32 |
 Representative Photo |
|
Technical Information |
|
|
|
Rail Type |
Combi Foot
|
Input Signal Type |
Current
|
Input Signal Range |
4...20 mA
|
Module Type |
Terminal Block
|
Power Requirements |
External
|
Coupling Method |
Opto Isolated
|
Output Signal Type |
Current
|
Output Signal Range |
4...20 mA
|
Housing Type |
Terminal block
|
Additional Data |
|
|
|
Input Impedence |
50 ohms
|
Input Maximum |
24 mA DC
|
Zero Setting (4.0 mA) Adjustment |
±5%
|
Span Adjustment (20 mA) |
±5%
|
Output Load/Loop Resistance |
£500 ohms
|
Output Supply Voltage (Min./Max.) |
18...30 VDC
|
Accuracy Input/Output |
0.1 % of FS
|
Transmission Frequency |
5 ms typical
|
Dielectric Isolation Input to Output |
2 kV
|
Dielectric Isolation I/O to Power Supply |
2 kV
|
Storage Temperature Range |
-20°C...+85°C
|
Operating Temperature Range |
0°C...+50°C
|
Wire Size |
#20...12 AWG 0.5...2.5 mm²
|
Clamp Screw Tightening Torque Nm (lb.in.) |
0.5 (4.38)
|
Mechanical Dimensions (WxLxH) mm (in.) |
8/89/68 (.31"/3.5"/2.68")
|
Insulation Stripping Length mm (in.) |
9 (.35")
|
Certifications |
CE, CSA
|
Suggested Accessories |
|
|
|
DIN-rail |
End bracket |
End plate/partition (AP/TW) |
Ferrules |
Markers (SchT) |
Marking pens |
Marking tags (DEK) |
Mounting brackets |
QB jumpers |
Tools |