| MCZ PT 100/3 CLP |
 Representative Photo |
|
| Technical Information |
|
|
|
| Rail Type |
TS 35
|
| Input Signal Type |
PT 100 (according to IEC 751)
|
| Input Signal Range |
0°C...300°C, 3-wire system
|
| Module Type |
Terminal Block
|
| Power Requirements |
Loop Powered
|
| Coupling Method |
Direct
|
| Output Signal Type |
Current
|
| Output Signal Range |
4...20 mA
|
| Housing Type |
Terminal block
|
Additional Data |
|
|
|
| Line Resistance
| max. 0.006°C/ohm
|
| Input Supply Current (Min./Max.) |
0.8 mA
|
| Output Load/Loop Resistance |
750 ohms at 24 V
|
| Output Supply Voltage (Min./Max.) |
max. 30 V / min. 9 V+20 AxRL
|
| Accuracy Input/Output |
typ. 0.2% max. 0.5% from FSR
|
| Linearity Input/Output |
<0.1% from FSR
|
| Temperature Coefficient |
max. ± 150 ppm/°C
|
| Dielectric Isolation Input to Output |
4 kV
|
| Dielectric Isolation I/O to DIN-Rail |
4 kV eff / 1 min
|
| Storage Temperature Range |
-20°C...+85°C
|
| Operating Temperature Range |
0°C...+50°C
|
| Wire Size |
#22...12 AWG
|
| Clamp Screw Tightening Torque Nm (lb.in.) |
Tension Clamp
|
| Mechanical Dimensions (WxLxH) mm (in.) |
6/91/63.2 (.24"/3.58"/2.49")
|
| Certifications |
UL, CSA, CE
|
Suggested Accessories |
|
|