connex-electronics.com Wago
Wago IO System - System Modules

Wago System Modules
Wago 750-628
Part Number Conformity Marking
750-628 CE
MODULE BUS EXTENSION, COUPLER MODULE
The internal data bus extension coupler module 750-628 replaces the fieldbus coupler/ controller on an I/O module assembly. It is the counterpart to the end extension module 750-627. The connecting cable is plugged into the RJ 45 input socket, providing the logical connection to the fieldus coupler/ controller via the internal data bus extension end module 750-627. The extension does not interfere with the fieldbus coupler/ controller, all bus module system functions remain unchanged. The RJ 45 output socket allows further extension of the system (max. 10 stations).
The supply voltage for the field side and the internal electronics can be input separately. Both levels are electrically isolated from each other. Two diagnostic LEDs give information about the supply voltage for both the internal and field side. Two LEDs in the RJ 45 socket indicate fault-free communication with the bus coupler. The extension module can be used as the last coupler module in the system (switch on matching resistor) or as a bridge between two I/O module assemblies.

Installation Notes:
In order to guarantee safe operating conditions when using the internal data bus extension modules 750-627/-628, the buscouplers must have the internal parameters set accordingly. Please order the WAGO extension setting tool 759-314 and use it to inform the buscouplers/ controllers 750-304, 750-306, 750-310, 750-319, 750-324, 750-333, 750-337, 750-339, 750-342, 750-804, 750-806, 750-19, 750-833, 750-837, 750-841, 750-842, including all variations, of the new operating parameters. Please complete the manufacturing number matrix on the right-hand side of the couplers when updating the firmware and internal operating parameters. On the left-hand side of the buscouplers, please use the markers (enclosed in 759-314) to identify the modules that have been activated / deactivated.
Technical Information
Characteristic Value
Max. no. of I/O bus modules 64 (IN THE WHOLE SYSTEM)
Distance between end module and coupler or coupler and coupler max. 5 m
Transmission medium SHIELDED COPPER WIRE (ETHERNET PATCH CABLE) 4 x 2 x 0.25 MM², TWISTED PAIR, DOUBLE SHIELDING
Buscoupler connection 2 x RJ 45 SOCKET (INPUT + OUTPUT)
Voltage supply DC 24 V (-15% / + 20%)
Start-up current 2.5 x CONTINUOUS CURRENT
Input current (max) 200 mA
Efficiency of the power supply 76%
Internal current consumption 150 mA
Total current for the I/O modules 400 mA
Voltage via power jumper contacts (max) DC 24 V (-15% / + 20%)
Current via power jumper contacts (max) DC 10 A
Operating temperature 0 °C ... + 55 °C
Storage temperature -25 °C ... +85 °C
Characteristic Value
Relative air humidity 95%
Vibration resistance acc. IEC 60068-2-6
Shock resistance acc. IEC 60068-2-27
Degree of protection IP 20
EMC immunity to interference acc. EN 50082-2 (96)
EMC emission of interference per EN 50081-1 (93)
Conformity marking CE
Cross section from [mm²] 0.08 mm²
Cross section to [mm²] 2.5 mm²
Cross section from [AWG] 28 AWG
Cross section to [AWG] 14 AWG
Weight 74.5 g
Color light gray
Height 65 mm
Height 2.56 in
Width 25 mm
Width 0.984 in
Depth 100 mm
Depth 3.937 in
Strip length from 0 mm
Strip length 0.33 in
Strip length to 0 mm