| Wago Fieldbus
Coupler |
 |
| Part
Number |
Standard |
Conformity
Marking |
Approvals |
| 750-333 |
EN 50170 |
 |
cULus, ABS*, BV*, DNV*, GL*, LR*,
RINA*, cULus-EX, KEMA |
| * 750-626 filter module is
absolutely necessary |
| PROFIBUS DP/V1 FIELDBUS COUPLER 12 MBaud
CARRIER RAIL DIN 35 CAGE CLAMP CONNECTION |
| This buscoupler interfaces the I/O modules
of the WAGO-I/O-SYSTEM 750 to PROFIBUS DP. When initializing, the buscoupler
determines the module structure of the node, to create the process image in
Profibus. In order to optimize addresses, the I/O modules with a bit width
smaller than 8 are grouped in one byte. It is furthermore possible to deactive
I/O modules and to modify the image of the node according to the connected
signals without having to modify the existing application. The diagnosis
concept is based on diagnostics according to the EN 50170 Standard. Therefore
the programming of modules is not necessary to interpret the diagnostic
information from each manufacturer. Note: GSD files required |
|
| Technical Information |
| Characteristic |
Value |
| Max. no. of nodes |
96 with repeater |
| Max. no. Of I/O points |
ca. 6000 (depends on Master) |
| Transmission medium |
Cu-cable acc. to EN 50170 |
| Max. length of fieldbus segment |
100 m ... 1200 m (depends on the baud rate / on
the cable) |
| Baud rate |
9.6 kBaud ... 12 Mbaud |
| Transmission time |
typ. 1 ms (10 Modules; 32 E, 32 A/Mod;at 12
Mbaud and digital Signals)max. 3.3 ms |
| Buscoupler connection |
1 x D-SUB 9; socket |
| UL 508 |
E175199, UL 508 |
| Standard |
EN 50170 |
| Conformity marking |
CE |
| Max. no. of I/O modules |
63 |
| Max. fieldbus input image (Byte) |
244 Byte |
| Max. fieldbus output image (Byte) |
244 Byte |
| Configuration |
via PC or PLC |
| Voltage supply |
DC 24 V (-25% / + 30%) |
| Input current (max) |
500 mA |
| Efficiency of the power supply |
87% |
| Internal current consumption |
200 mA |
| Total current for the I/O modules |
1800 mA |
| Isolation |
500 V system / supply |
| Voltage via power jumper contacts (max) |
DC 24 V (-25% / + 30%) |
| Current via power jumper contacts (max) |
DC 10 A |
|
| Characteristic |
Value |
| Operating temperature |
0 °C ... + 55 °C |
| Storage temperature |
-25 °C ... +85 °C |
| Relative air humidity |
95% |
| Vibration resistance |
acc. IEC 60068-2-6 |
| Shock resistance |
acc. IEC 60068-2-27 |
| Degree of protection |
IP 20 |
| EMC immunity to interference |
acc. EN 50082-2 (96) |
| EMC emission of interference |
acc. EN 50081-2 (94) |
| EMC marine applications - noise proof |
gem. Germanischer Lloyd (1997) |
| EMC marine applications - noise
transmission |
gem. Germanischer Lloyd (1997) |
| Cross section from [mm²] |
0.08 mm² |
| Cross section to [mm²] |
2.5 mm² |
| Cross section from [AWG] |
28 AWG |
| Cross section to [AWG] |
14 AWG |
| Weight |
182 g |
| Color |
light gray |
| Height |
65 mm |
| Height |
2.56 in |
| Width |
51 mm |
| Width |
2.008 in |
| Depth |
100 mm |
| Depth |
3.937 in |
| Strip length from |
8 mm |
| Strip length to |
9 mm |
| Strip length |
0.33 in |
|
|