connex-electronics.com Moeller Electric
Moeller Miniature Circuit Breakers

  
Moeller Miniature
Circuit Breakers
FAZ-Series
Branch Circuit Breakers (UL489)
General Information
Breakers - Trip Characteristic C (Use with Inductive Loads)
Breakers - Trip Characteristic D (Use with Highly Inductive Loads)
Accessories
Bus Bar System
Incoming Supply Terminals
Technical Data
Dimensions
FAZ-Series Supplementary Circuit Breakers (UL1077)
General Information
Breakers - Trip Characteristic B (Use with Resisitive or Slightly Inductive Loads
Breakers - Trip Characteristic C (Use with Inductive Loads)
Breakers - Trip Characteristic D (Use with Highly Inductive Loads)
Accessories
Bus Bar System
Incoming Supply Terminals
Protective Accessories
Technical Data
Dimensions
Application Notes
Applying Branch Circuit Breakers and Supplementary Protectors in North America (.pdf)
 
FAZ Series - Branch Circuit Breakers (UL-489) - General Information
 
Branch Circuit Breaker - General Information
 
Moeller has just expanded its FAZ line of miniature circuit breakers to include devices that are listed and certified as molded case circuit breakers per UL 489 and CSA 22.2, No. 5-02. These new branch circuit breakers, called FAZ-NA and FAZ-RT, are ideal for the protection of power supplies, control power transformers, HVAC, refrigeration equipment, florescent lighting (to 20A) and many other applications requiring a primary protective device.
Moeller - Faz Series Branch Circuit Breakers  
Flexible Product Range
Moeller’s FAZ Branch Circuit Breakers are available in one, two and three pole configurations with 20 different current ratings ranging from 0.5A to 40A. All breakers are available in both C and D tripping curves, offering protection from 5 to 10 and 10 to 20 x the continuous rating of the device (In). Two and three pole devices can be used in solidly grounded circuits up to 480V AC. The entire line offers short circuit ratings of 10kA regardless of voltage applied.
 
Many installation options
FAZ Branch Circuit Breakers are available in two terminal configurations; standard box terminals that accept multiple conductors and ring-tongue terminals, ideally suited to the demanding requirements of the semi-conductor industry. All breakers mount on standard 35mm DIN-rail. Bus Connectors and Feeder Terminals facilitate mounting and wiring of multiple miniature circuit breaker arrays in control panel assemblies. Power to the circuit breakers can also be fed from the line or load side.
 
Standard features enhance safety
As with most products from Moeller, FAZ breaker terminals provide finger and back-of- hand protection to guard against accidental contact with live parts. A color-coded red/green indicator provides immediate visual indication of device status and isolation function (green for OFF, red for ON). All FAZ breakers incorporate a “tripfree” mechanism. This prevents the trip function from being defeated by holding the operator in the ON position. In addition, all FAZ branch circuit breakers are UL listed and CSA certified for fuseless protection of smaller AWG 18 and 16 conductors!
 
Worldwide acceptance RT - Allows Ring Terminal Connections
FAZ-NA (RT) Molded Case Circuit Breakers are UL Listed for use in the United States in accordance with NFPA 70 (NEC). The devices comply with UL 489 and CSA 22.2 No. 5-02, meeting the requirements for Molded Case Circuit Breakers. These devices also comply with IEC 60947-2 and are CE compliant.
Approvals
 
Tripping characteristics
Moeller FAZ-NA(RT) branch circuit breakers are available with “C” and “D” tripping characteristics. C-curve devices are suitable for applications where medium levels of inrush current are expected. Applications include small transformers, lighting, pilot devices, control circuits, and coils. C-curve devices provide a medium magnetic trip point.
Devices with a “D” curve are suitable for applications where high levels of inrush current are expected. The high magnetic trip point prevents nuisance tripping in high inductive applications such as motors, transformers, and power supplies.
Even though not required by NEC or CEC for Branch Circuit Breakers, Moeller’s FAZ-NA(RT) devices are current limiting, which means they interrupt fault currents within one half cycle of the fault. Current limiting devices offer superior protection by reducing peak letthrough current and energy.
 
FAZ Series Branch Circuit Breaker Features