CT-2MR CURRENT TRANSFORMER
Basic specifications
Model and rated voltage CT-2MR (100 A), CT-2MR (120 A), CT-2MR (150 A), CT-2MR (200 A), CT-2MR (250 A), CT-2MR (300 A), CT-2MR (500A), CT-2MR (600A)
Accuracy (50/60 Hz) JIS-Class 1.0 (±1 % at rated value)
Rated load 2 VA
Secondary current 5 A (all models)
Conductor voltage rating 1150 V AC
Dimensions, mass (see figures below)
Accessories None
CT-2MR CURRENT TRANSFORMER (Dimensions, unit: mm)
CT-2MR CURRENT TRANSFORMER (Connection figure)
Wiring:
Pass the wire through center of the C.T. When measuring under 100 A, use the equation below to find the number of times that the wire is to be passed through. Number of turns = (Primary current of C.T.) ÷ (Maximum value measured) However, in order to make the number of turns a full number, select the primary current or full scale.