| Hioki Data Logger Series
|
 |
3636-20 CLAMP LOGGER
|
| Overview |
| Easy and convenient, clamp-on current recording |
- Up to 32,000 measurements data can be collected with the optional
3911-20 for processing by PC
- Effective value rectifier method for correct measurement
- Special software bundled with the
3911-20 enables storing of the recording time, interval, start, end, method and comments in the instruments memory
- Non-volatile memory preserves collected data even when the battery is depleted
|
|
 |
|
|
| Options (click for picture/details)
|
9650 CLAMP ON SENSOR - 100 A f.s., 3 m (9.84 ft) length, Primary current: 100 A AC, Secondary current: 100 mA AC, ±1.5 % rdg. ±0.03 % f.s.
|
9651 CLAMP ON SENSOR - 500 A f.s., 3 m (9.84 ft) length, Primary current: 500 A AC, Secondary current: 500 mA AC, ±1.5 % rdg. ±0.03 % f.s.
|
9632 CONNECTION CABLE - Supplied as standard with the
3636-20 1 m (3.28 ft) length, Equipped with an instrumentation sensor, Supports a wide variety of sensors, plug (Ø2.5 mm) - cord open, Cable length: 1 m (3.28 ft)
|
3911-20 COMMUNICATION BASE - Communication software for the PC is supplied as standard
|
3912-20 COMMUNICATION BASE with USB Interface - Communication software for the PC is supplied as standard
|
9637 RS-232C CABLE - 9pin-9pin/Cross, 1.8 m (5.91 ft) length
|
9638 RS-232C CABLE - 9pin-25pin/Cross, 1.8 m (5.91 ft) length
|
|
|
| Basic specifications
|
| Measurement items |
AC Current (with clamp-on sensor, sold separately)
|
| Input channels |
2 channel |
| Measurement range |
0.00 to 50.00 A, 0.0 to 500.0 A (True RMS) |
| Accuracy |
±2.5 % rdg. ±8 dgt. (at 50/60 Hz, combined accuracy with clamp-on sensor)
|
| Data memory |
16000 data × 2ch (1-minute interval, total 11 days), 32000 data × 1ch (1-minute interval, total 22 days)
|
| Recording interval |
1 to 30 seconds, 1 to 60 minutes, 15 settings
|
| Power supply |
4 x 1.5 V, LR03 (AAA) alkaline dry cell batteries, lifetime approx. 1 year (recording interval 1 minute)
|
| Dimensions, mass |
57.5 mm(2.26 in)W × 86.5 mm(3.41 in)H × 30 mm(1.18 in)D, 130 g (4.6 oz)
|
| Accessories |
LR03 alkaline dry cell batteries (4), 9632 CONNECTION CABLE (for alarm output, 1)
|
|
| 3630 DATA LOGGER Series product catalog.pdf (645 KB)
|
Back |