3157-01 AC GROUNDING HiTESTER
|
| Overview |
| Protective ground tester indispensable for standard certification
|
Designed to measure whether the metal enclosure of electrical equipment is connected to the ground terminal at sufficiently low resistance levels. It also can be used to evaluate the grounding conditions of large-scale electrical installations. Measurement is carried out by using a high current according to the specifications of the measurement object, and determining the voltage drop at the measurement point. Reference values are as set out in the various safety standards. The
3157-01 can carry out measurements in accordance with the stipulations of multiple standards.
|
|
 |
|
|
| Options (Click for picture)
|
This product cannot be used alone. For measurement, two
9296 or one each of
9296 and
9297 are required.
|
9296 CURRENT PROBE - alligator clip type, 1.5 m (4.92 ft) length
|
9297 CURRENT APPLY PROBE - with switch type, 1.5 m (4.92 ft) length
|
9613 REMOTE CONTROL BOX - single
|
9614 REMOTE CONTROL BOX - dual
|
9442 PRINTER - 10 m (32.81 ft), 10 rolls/1 set
|
9443-02 AC ADAPTER - for printer, for use in EU)
|
9443-03 AC ADAPTER - for printer, for use in USA
|
9446 CONNECTION CABLE - for connecting the
3157-01 to the
9442
|
1196 RECORDING PAPER - 25 m (82.03 ft), 10 rolls/1set
|
9518-02 GP-IB INTERFACE - |
9593-02 RS-232C INTERFACE |
User Guide
|
|
| Basic specifications
|
| Measurement mode |
Low resistance, AC 4-terminal method |
| Generator section |
Current generator principle: PWM constant current control,
Current setting range: 3.0 A to 31.0 A (0.1 A resolution), into 0.1 Ohm load,
Maximum output power: 130 VA
*1 (at output terminals) *1 Subject to derating according to ambient temperature (80 % at 40 °C)
Frequency: 50 Hz or 60 Hz sine wave,
Soft start function: Apply current only after checking load connection
|
| Monitor section |
Resistance measurement: 0 to 1.800 Ohm (0.001 Ohm resolution),
Accuracy: ±2 % rdg. ±4 dgt. (after zero-adjust),
Current monitoring range: 0 to 35.0 A AC (0.1 A resolution),
Monitoring cycle: 2 times/second |
| Other functions |
Timer setting: Counts down time after start until preset time, or shows elapsed time after start,
Setting range:
0.5 to 999 second, Comparator: Pass/Fail evaluation using preset upper/lower limit, I/O output,
Memory function: max. 20 settings (with save/load)
|
| Display |
Fluorescent tube digital display |
| Power supply |
100 to 120 V, 200 to 240 V AC (auto-switching), 50/60 Hz
|
| Dimensions, mass |
320 mm(12.60 in)W × 90 mm(3.54 in)H × 263 mm(10.35 in)D, 7 kg (246.9 oz)
|
| Accessories |
Power cord(1), Spare fuse(1), Shorting bar(2)
|
|
|
|